Control and protection panel for 2 single-phase/three-phase pumps V2P TOSACNO | ADAJUSA
Control and protection panel for 2 single-phase/three-phase pumps V2P TOSACNO | ADAJUSA

Control panel V2P for 2 single-phase/three-phase pumps controlled by pressure switches- TOSCANO

€545.40 Tax included

€450.74 tax excl.

Compact control and protection panel for 2 single-phase or three-phase pumps up to 12A with automatic alternation between them by means of pressure switches , 230/400Vac power supply (selectable). Overload adjustment, detection of lack of air in the boiler, control of lack of water by built-in hydro level or buoy.


Reference: V2P




Representative image for illustrative purposes, the supplied article will correspond to the indicated specifications.   

No queries yet, leave the first!
 
Compact control and protection panel for 2 single-phase or three-phase pumps up to 12A with automatic alternation between them by means of two pressure switches (high pressure switch and low pressure switch), selectable 230Vac or 400Vac power supply. By means of a built-in relay, it allows the manual adjustment of maximum intensity for the protection of the pumps against overload, detection of lack of air in the boiler, control for lack of phase, control of lack of water by built-in hydro level or buoy.


The panel has a panel on the front with function or alarm indicator lights (supply voltage to the panel, pump running, pump failure alarm, low level alarm), as well as buttons for the start and stop of the pump and a reset button that allows the unit to be reset after an alarm due to overload or lack of phase in the boiler. It has a load cut-off switch for forced stopping that stops the motor and does not allow it to start under any circumstances.

Automatic operation of the pumps according to the values and protections established or manual operation that causes the forced start of the pump, while the thermal protection of the pump remains active. Automatic switching of the pumps due to failure, thermal failure or deactivation of one of them, remote control input, independent voltage-free contact alarm outputs for general alarm and a second one for starting the boiler compressor. Protection of the pump against overload, lack of phase (three-phase pumps) and protection against anti-seizure of the pumps so that when they are in automatic state, the equipment applies one second of operation every 23 hours of inactivity, to avoid seizing and deterioration in long periods of rest and general load cut-off switch. It has a port for the connection of a remote control Wifi module.







Characteristic:

  • Manufacturer: Toscano
  • Reference: V2P
  • Control and protection of two pumps with automatic alternation by means of two pressure switches
  • Dual voltage 230/400Vac
  • Automatic switching of the pumps in case of failure or deactivation of one of them
  • Electronic overload relay adjustable from 0 to 13A per pump
  • Detection of lack of air in the boiler
  • Phase loss protection
  • General load break switch
  • Disconnector with calibrated fuses
  • power contactors
  • MAN-0-AUT buttons for automatic operation (according to established controls and protections) or manual operation of the pump (forced start of the pump, while the thermal protection of the pump remains active) and stop (stops the motor and does not allow its boot under any circumstances)
  • Pilot lights for voltage, lack of water, running and pump overload
  • Overload alarm reset button (RESET)
  • Control of lack of water by hydro level (incorporated) or buoy
  • Remote control socket by contact or voltage (6 to 400 Vac/Vdc)
  • Pump alarm and lack of air contact output
  • All control elements at 12 Vdc for greater safety
  • High protection cable glands
  • Circuit breaker



Technical characteristics:

  • Power supply: 230/400Vac (selectable) – 50/60Hz
  • Allowable voltage variation: +10% - 15%
  • Maximum current: 12A (per pump) AC3
  • Overload setting: 0 - 13A
  • Underload setting:
  • Voltage/Sensitivity (in probes) : 24Vac / 9Kohm
  • Probes sensitivity: 10K ± 15%Ω
  • Remote control connection: Contact or voltage 6…40Vac/dc
  • Pressure switch connection: 12Vdc - 10mA
  • Input connection (power): Direct to switch
  • Output connection (motors): Direct to contactor 4 mm2
  • Fixation: Mural by clamping forks or claws
  • Working temperature: -10 +55ºC
  • Degree of protection: IP56
  • Measurements: 220 x 300 x 120mm
  • Weight: 3.5kg



Connection:









For more information, you can download the technical sheet by clicking on the "Attached Files" tab.

Material for professional use, install in compliance with the regulations in force at the place of installation.